CO2 Meter RAD-0102-6 Remote Storage Safety 3 Alarm
The Remote CO2 Storage Safety Alarm is designed to protect customers and workers near stored carbon dioxide (CO2)
CO2 alarms are critical in restaurants, breweries, wineries, beverage dispensing areas, dry ice storage, laboratories, cultivation facilities, or anywhere more than 100 lbs. of compressed CO2 is stored or produced
- Wired CO2 Monitor & Remote Display
- Designed to Meet All-State Fire Codes
- Meets NFPA, IFC, and NBIC Requirements
- Meets OSHA and NIOSH TWA Standard
- Meets EU: EH40 - Workplace Exposure Limits
- Meets UK: Health and Safety Work Act
- Meets AU: AS5034 Installation/Use of inert gases for beverage dispensing
- UL listed for compliance
The Monitor has both audible and visual alarms. 3 built-in relays are triggered at 5,000 ppm TWA, 1.5% CO2, and 3% CO2 that can control an exhaust fan or send an alarm to the fire department or monitoring company. This meets state and local municipality inspection code requirements around stored CO2.
Features
- NDIR technology
- More flexible - extend remote up to 300 feet from the main unit
- Designed to ensure fire code compliance in any State
- Reliable connection with a standard Ethernet cable (25 ft. included)
- Large display clearly indicates the current CO2 level and temperature
- 3 relays automatically control fans to ventilate confined spaces
- 4-20 mA output to allow for remote display of values
- 88 dB audible and visual alarms on both units
- IP54 Enclosure - prevents water damage during wash-down
- 100% clean look – all cables can be hidden
Specifications
- Measurement Range: 0-5% (50,000ppm) CO2 Sensor
- Alarms: 5,000 ppm TWA, 1.5% CO2, 3% CO2 (configurable).
- Alarm Response Time: < 60 seconds
- Operating Temperature: 0-50°C (32-122°F)
- Calibration: Manual with test gas or factory calibration
- Sensor Life Expectancy: 15 years
Electrical
- Power Supply: 110-220VAC 50/60 Hz to 12VDC Power Adapter
- 24VDC hard-wired power option (cable included)
- Power Consumption: 3 Watts
- 6VDC battery backup connections
- Relays: Peak Current < 2A @ 30VDC or 250VAC, SPDT
- Relay Color Coding: Red & White = Normally Open Blue & White = Normally Closed
Warranty
- 1 year - See CO2Meter Terms and Conditions.